1-866-494-4610

BAPI BA/VOC10-V-BB VOC Sensor Rugged Enclosure 0-10Vdc

BAPI BA/VOC10-V-BB VOC Sensor Rugged Enclosure 0-10Vdc
Images for general purposes only. Actual may be different than depicted.
BAPI BA/VOC10-V-BB VOC Sensor Rugged Enclosure 0-10Vdc BAPI BA/VOC10-V-BB VOC Sensor Rugged Enclosure 0-10Vdc

BAPI BA/VOC10-V-BB VOC Sensor Rugged Enclosure 0-10Vdc

SKU: BA/VOC10-V-BB
Rating:
Quantity Price Stock
Usually Ships 3-5 Days
Usually Ships 3-5 Days
$193.84     /ea
Usually Ships 3-5 Days
0
$0.00
0
$0.00
0
BA/VOC10-V-BB

Humans respirate Volatile Organic Compounds (VOCs) as well as CO2. The BAPI sensor measures these VOCs and indicates when a space is occupied just as well as a CO2 sensor.

The advantage of the VOC sensor is that it measures air contaminants from other sources besides respiration, such as building materials, cleaners, perfumes and furniture and carpet off-gassing. Using this sensor for Demand Controlled Ventilation then is a way of achieving true indoor air quality, rather than just CO2 dilution.

A further benefit is that it requires no additional work on your part. That’s because the sensor converts the VOC reading to a CO2 equivalent level. This lets you use ASHRAE’s CO2-based VRP schedule to ventilate. (More information on the CO2 equivalent output is available on the “Application Notes” tab below.)

The Duct unit samples duct air using an aspiration tube. The Rough Service unit features a ventilated BAPI-Box and is ideal for rough service areas such as outdoor air plenums, equipment rooms, attics, green houses and warehouses.

  • Achieves True Indoor Air Quality Rather Than CO2 Dilution
  • Output is Correlated to a CO2 Value for Easy DCV Setup
  • Quick Response Sensor with Aspiration Tube or Ventilated BAPI-Box
Power 12 to 24 VDC, 50 mA Peak; 18 to 24 VAC, 1.5 VA Peak
Enclosure Material Polycarbonate, UL94 V-0
Operating Environment (Humidity) 0 to 95% RH Non-Condensing
Unventilated BAPI-Box Rating NEMA 4, IP66
Start-Up Time 15 minutes
Operating Environment (Temperature) 32F to 122F (0C to 50C)
VOC Sensing Element Micro-machined Metal Oxide
VOC Detection Range 0 to 2,000 ppm CO2 Equivalent
Response Time Less Than 60 Seconds
Analog Outputs 0 to 5VDC or 0 to 10VDC >10KΩ impedance; VOC Contaminants: 0 to 2,000 PPM CO2 Equivalent

Q & A: Ask the Questions, share answers